|
It's a Switch |
Meltric Decontactors™ Series Plugs and Receptacles
are approved as an NEC 'Line of Sight'
Disconnect |
•
UL Subject 2682 |
Branch Circuit Disconnect Switch |
|
Motor Circuit
Disconnect Switch |
• CSA C22.2 No. 4 |
Branch Circuit
Disconnect Switch |
|
No 14 |
Motor Circuit
Disconnect Switch |
|
|
It's a Plug &
Receptacle |
|
Superior Safety with Dead Front
Construction |
• UL
1682 & UL 1686 |
• CSA
C22.2 No. 182.1 |
|
It's
the World's Only UL 'SWITCH RATED PLUG &
RECEPTACLE' |
UL
Subject 2682 is a new standard that UL has established for products,
like Meltric's Decontactor Series, that provide the performance and
capabilities of disconnect switching capabilities from UL 98 (
Enclosed & Dead Front Switches) and UL 508 (Industrial Control
Equipment) with the plug & receptacle requirements in UL
1682. |
|
Key Performance Tests – UL Subject 2682 – Switch
Rated Plugs & Receptacles |
• Short-Circuit
Withstand: |
≥
10kA (pf = .40 - .50) |
• Short-Circuit
Make: |
≥
10kA (pf = .40 - .50) |
•
Overload-Locked Rotor: |
50
operations @ 600% of full load motor current (pf = .40 -
.50) |
•
Overload-General Use Devices: |
50
operations @ 150% of rated current (pf = .75- -
.80) |
• Temperature
Rise: |
<
30°C |
• Voltage
Withstand: |
1000
V + 200% of rated voltage |
• Electrical
Endurance: |
6000
cycles @ rated current & voltage (pf = .75 -
.80) |
• Mechanical
Endurance: |
4000
cycles |
|
|