[ Automatic-Watertight ] [ Butt-Style-Pressure-Contacts ] [ Dead-front-Construction ] [ Hazardous Duty Plug and Receptacle ] [ Silver-Nickel Contact Materials ] [ Spring-Assisted Terminals ] [ Switch Rated ]
Hazardous Duty Plug and Receptacle
DXN Series |
 | The DXN is unique
in that it is a hazardous duty plug and receptacle that allows users to
make and break under load. It is the ideal plug and receptacle choice for
Class I Div II locations. The NEMA 4X and IP67 watertight
seal for the DXN series is automatically achieved as soon as the contacts
are closed. Each device is made of self extinguishing non-static glass
reinforced polyester (PBT) material that offers outstanding resistance to
mechanical abuse and chemicals.
DXN products are available in 20,
30 and 60 amp sizes at 480V and for applications where additional control
circuits are required, units are also available with two pilot
contacts. |
Hazardous Duty Certifications
CSA
Class I
Division 2 Gr A,B,C,D |
• Class I – Indicates suitability for
use in applications where flammable Gases, Vapors, or ;Mists may be
present.
• Division 2 –
Indicates suitability for use where exposure to the hazard occurs
under abnormal
conditions.
• GR A,B,C,D –
Indicates suitability for use in areas that may contain
Acetylene, Hydrogen, Ethylene, or Propane. |
|
Class II
Division 2 Gr E,F,G |
• Class II –
Indicates suitability for use in applications where dust may
occur.
• Division 2 –
Indicates suitability for use where hazard exposure occurs under abnormal conditions.
• GR E,F,G –
Indicates suitability for use in areas where Magnesium, Coal or
Grain dust may
occur. |
ATEX
II 2 G/D
DUST T85°C EEx ed IIC T6 LCIE 99 ATEX 6027 X |
• II – Indicates
suitability for installation in surface applications (as opposed
to underground mine applications).
• 2 –
Indicates suitability for use where a high level of protection is required and where the presence of an explosive atmosphere is likely to occur.
• G/D – Indicates suitability for installation in areas that may contain flammable gases, vapors/mists, or
dusts.
• T85°C – Indicates a maximum surface temperature of the product of 85°C, at 40°C ambient. The temperature class
is T6.
• EEx ed – Indicates that explosion protection is provided with
(e) increased safety in the
conductor termination area, and (d) explosion proof chambers for
making and breaking the current that can withstand the pressure of internal ignition and that prevent arcs, flame or other
ignition events from being communicated to the surrounding atmospere.
•
IIC – Indicates suitability for installation in areas where exposure to any type of gas, including the most dangerous subdivision C gases may occur.
• LCIE 99 ATEX 6027 X
– Indicates that the DXN’s ATEX certification was approved
by LCIE Laboratory in
1999. |
*DXN1 and DXN3 sizes only. DXN6 CSA listings expected soon. Consult factory.
|
DX Series |
 | Meltric’s DX Series plugs and
receptacles are heavy-duty metallic devices that are safe for use in
hazardous environments. They are available in 20, 30, 60 and 100A
sizes. Each device is EEx ed IIC T6 rated to CENELEC standards
EN50014/18/19 Zones 1, 2, and 21. DX’s have additionally been tested
and approved by ETL for operation under load in a gaseous environment
(14.5% acetylene). This is a key performance test required for Class 1,
Division 1 products.
The DX’s rugged construction, compact size,
cost-effective design, IP 65 rating and unique safety and operating
features make them a good choice for refineries, petroleum platforms,
chemical and pharmaceutical plants, grain silos and other similar
potentially hazardous applications. |
DX Series Products Comply with:
CSA
• IEC/EN
60309-1
• IEC/EN 60947-3,
AC22
• EN 50014 /18/19
Zones 1 &2
• EEx ed
IIC T6; CENELEC
certified
• IEC 61241-3
for Zones 21 &22
|
|